Range

SIZE Un (V AC) In (A) REFERENCE
NHC3 400V 315 380445
355 380450
400 380455
NH3 400V 500 380465
630 380470

Technical data

Rated voltage 400V AC +10%
Rated currents 315A...630A
Rated breaking capacity 120kA
Operating class gG
Rated frequency 42...62Hz
Storage temperature -40°C ... 90°C
Operating temperature * -40°C ... 80°C
* For ambient temperatures higher than 25ºC it is necessary to apply a derating in maximum current.

Standards

IEC/EN 60269-1
IEC/EN 60269-2
RoHS Compliant

Dimensions

A B C D E F G H I J K L
NHC3 68 62 71,5 150 25 10 9,5 6 53 60 60 84
NH3 68 62 73 150 32 10 9,5 6 70 60 75 87

Weight  630gr (NHC3) | 1,02kg (NH3)

t-I characteristics

Cut-off characteristics

Power dissipation

RATED CURRENT
(A)
REFERENCE POWER DISSIPATION
(W)
PREARCING I2t
(A2s)
TOTAL I2t 230V
(A2s)
TOTAL I2t 400V
(A2s)
315 380445 19,5 421200 526600 621100
355 381450 22,2 533100 666500 786100
400 381455 25,5 796400 995650 1174300
500 381465 32,0 958700 1411000 1877500
630 381470 38,5 1870600 2753000 3663200

Other sizes

U 400V 400V 400V 400V
IN 10A...100A 125A | 160A 50A...250A 100A...400A
Breaking capacity 120kA 120kA 120kA 120kA