| SIZE | Un (V AC) | In (A) | REFERENCE |
| NH00 | 400V | 125 | 380070 |
| 160 | 380075 |
| Rated voltage | 400V AC +10% |
| Rated currents | 125A | 160A |
| Rated breaking capacity | 120kA |
| Operating class | gG |
| Rated frequency | 42...62Hz |
| Storage temperature | -40°C ... 90°C |
| Operating temperature * | -40°C ... 80°C |
| * For ambient temperatures higher than 25ºC it is necessary to apply a derating in maximum current. | |
IEC/EN 60269-1
IEC/EN 60269-2
RoHS Compliant
| RATED CURRENT (A) |
REFERENCE | POWER DISSIPATION (W) |
PREARCING I2t (A2s) |
TOTAL I2t 230V (A2s) |
TOTAL I2t 400V (A2s) |
|---|---|---|---|---|---|
| 125 | 380070 | 7,2 | 49300 | 78300 | 110300 |
| 160 | 380075 | 9,5 | 85000 | 134980 | 190000 |
![]() |
![]() |
![]() |
|
| NH00 ST 690V/800V fuse base | Microswitch for NH fuse links | NH ST 1000V AC/DC Fuse puller | |
| U | 690V 800V |
250V AC | 1000V DC |
| In | 160 A | 5 A | |
We use cookies from third party services for a better user experience. If you continue browsing you are giving your consent for the acceptance of our Cookies Policy.