Range

SIZE Un (V AC) In (A) REFERENCE
NH00 800V 25 369030
32 369035
40 369045
50 369050
63 369055
80 369060
100 369065

Technical data

Rated voltage 800V AC +10%
Rated currents 25A...100A
Rated breaking capacity 120 kA
Utilization category gS
Rated frequency 42Hz...62Hz
Storage temperature -40°C ... 90°C
Operating temperature * -40°C ... 80°C
* For ambient temperatures higher than 25ºC it is necessary to apply a derating in maximum current.

Standards

IEC/EN 60269-1 Fuse links – general requirements
IEC/EN 60269-2
RoHS Compliant

Dimensions

A B C D E F G H I J K L
49 44 52 78,5 15 10 9,5 6 29 35 47 59

Weight  180gr

t-I characteristics

Cut-off characteristics

Power dissipation

RATED CURRENT
(A)
REFERENCE POWER DISSIPATION 0,8·In
(W)
POWER DISSIPATION In
(W)
PREARCING I2t
(A2s)
OPERATING I2t
(A2s 800V ~)
25 369030 2,4 4,1 100 385
32 369035 2,6 4,6 260 990
40 369045 3,3 5,6 400 1540
50 369050 3,7 6,1 790 3025
63 369055 4,2 6,8 1620 6170
80 369060 4,8 8,3 3170 12100
100 369065 6,8 10,9 5200 19900

Other sizes

U 800V AC 800V AC
IN 100A...200A 250A...400A
Breaking capacity 120kA 120kA

Privacy Preference Center